• PRODUCTS
  • KNOWLEDGE
  • RESOURCES
  • COMPANY

›Commander

Overview

  • DALION

Introduction

  • Introduction

Hardware

  • Hardware Installation

Web User Interface

  • Web User Interface

BACnet Interface

  • BACnet Interface

Room Light Control

  • Room Light Control

Schedule

  • Schedule

Commander

  • Commander

View

  • View

USB Console

  • USB Console

DALION Tool

  • DALION Tool

Remote CLI Tool

  • Remote CLI Tool

API

  • API

Commander

The Commanders allow sending multiple commands in sequence. The sequence can be executed once, executed a number of times or executed until stopped manually.

The Commanders can be started or stopped from a schedule, a DALI-2 button, the occupancy of a Room Light Control, BACnet or the web interface.

The commands can be used to control one of the following:

  • Control the light intensity of a group or channel.
  • Send a command to a group or channel (Recall Scene, Recall Min Level, etc.).
  • Control the colour of group or channel.
  • Enable or disable a DALI-2 sensor or button.
  • Send a command to a Room Light Control (Start Daylight Harvesting, Stop Demand Response, etc.).
  • Enable or disable a schedule.
  • Start or stop the execution of another commander.

Image of Commanders

Specifications

There are 64 commanders that can execute up to 12 commands each.

Considering that a command can be configured to start another commander, the total number of commands for a single commander Start can be extended beyond the limitation of 12 command for a single commander.

Parameters

Name

The name of the commander is limited to 16 characters.

Execute Count

The number of executions of the commander. This also allows disabling the commander.

Steps

The list of commands to be executed.

Destination Type

The destination type.

Destination TypeDescription
DisabledDisabled
Group, ChannelLighting intensity
Group, Channel - CommandCommand for lighting
Group, Channel - ColourLighting colour
Input DeviceCommand for sensor and button
RLC - CommandCommand for a Room Light Control
Schedule - CommandCommand for a Schedule
Commander - CommandCommand for a Commander
Commanders - CommandCommand for the Commanders
Disabled

The step is ignored.

Group, Channel

The value is the light intensity for a group or channel.

Group, Channel - Command

For the list of available commands refer to the section "Multi-State Output Object - Command Control of Lamp, Group and Channel".

Group, Channel - Colour

The value is the light intensity and colour for a group or channel.

Input - Command

Allows to enable or disable a DALI-2 sensor or button.

RLC - Command

For the list of available commands refer to the property section "Command" of the "Loop Object - Room Light Control".

Schedule - Command

Allows to enable or disable a schedule.

Commander - Command

Allows to start or stop a specific Commander. The destination is a single Commander and the value is the command Start or Stop for this Commander.

Commanders - Command

Allows to start or stop a Commander.

Fade Time

The fade time used by the command with the destination type Group, Channel.

Delay

The delay in seconds before the execution of the step.

← ScheduleView →
  • Specifications
  • Parameters
    • Name
    • Execute Count
    • Steps
Documentation
BACnet DALI Lighting ControllerBACnet HMI5 AppBACnet Explorer App
Support
Contact Us
Products
BACnet DALI Lighting ControllerBACnet HMI5 AppBACnet Explorer App
BACMOVE