Key Takeaways
- A Modbus DALI gateway maps DALI lamps, groups and scenes to Modbus registers, so a PLC, SCADA or energy management system can control DALI lighting.
- Modbus TCP runs over Ethernet and is the simplest way to connect DALI to an IP-based control system.
- The register map is what matters most: it defines which lamps, groups, scenes and colour settings you can control.
- DALION is a Modbus TCP DALI gateway that also supports BACnet/IP, sACN, Art-Net and a REST API.
Why control DALI with Modbus?
Modbus is one of the most widely used protocols in industrial automation. PLCs, SCADA systems, energy management systems and many building controllers can read and write Modbus registers. DALI, on the other hand, is a dedicated lighting bus that these systems cannot talk to directly.
A Modbus DALI gateway connects the two. It lets a factory, warehouse, parking garage, tunnel or utility site control its DALI lighting from the same system that already runs its machines, pumps or energy monitoring, without adding a separate lighting control platform.
Modbus TCP or Modbus RTU?
- Modbus TCP carries Modbus over Ethernet. It uses the existing IP network, supports several clients, and is the usual choice for new installations.
- Modbus RTU uses RS-485 serial wiring. It is common on older equipment and on long serial runs.
Check which variant your PLC or SCADA system uses before choosing a gateway.
How a Modbus DALI gateway works
The gateway acts as a Modbus server. Each Modbus register corresponds to a DALI function, such as the level of one lamp, the level of a group or a scene to recall. When the Modbus client writes a value to a register, the gateway sends the matching command on the DALI bus and handles DALI addressing and timing.
For example, with DALION each DALI channel has a block of 128 holding registers:
| Register offset | Function |
|---|---|
| 0–63 | Lamp levels (64 lamps) |
| 64–79 | Group levels (16 groups) |
| 80 | Broadcast level |
| 81–96 | Scene recall per group |
| 97 | Scene recall broadcast |
| 98–113 | DT8 colour temperature per group |
| 114 | DT8 colour temperature broadcast |
| 115–116 | Commander start and stop |
Register values range from 0 to 255. For a level register, 0 is off and 255 is 100%, so writing 128 to offset 64 (the first group register) sets that group to about 50%. For a scene register, writing 3 recalls scene 3.
Some Modbus clients number holding registers from 40001 instead of 0. Check the addressing convention of your PLC or SCADA software when you set up the register map.
What to check in a Modbus DALI gateway
| Question | What to check |
|---|---|
| Modbus variant | Modbus TCP, Modbus RTU, or both. |
| Register map | Which lamps, groups, scenes and broadcast commands are available, and whether the map is documented. |
| Number of devices | DALI channels per gateway and DALI devices per channel. |
| Colour control | DT8 colour temperature support for tunable white. |
| Local logic | Whether the gateway can also run schedules, occupancy and daylight control on its own. |
| Other protocols | BACnet, DMX or an API, if other systems also need to control the lighting. |
DALION as a Modbus DALI gateway
BACMOVE DALION acts as a Modbus TCP server with 512 holding registers: one block of 128 registers for each of its up to four DALI channels. A Modbus TCP client can set lamp, group and broadcast levels, recall scenes, adjust DT8 colour temperature and start or stop commanders.
The same DALION can also be a BACnet DALI gateway, receive DMX512 over sACN and Art-Net, and expose a REST API. It runs room light control, daylight harvesting and schedules locally, and supports 64 DALI lamps and 32 DALI-2 input devices per channel.
See the complete DALION Modbus TCP register map in the documentation, or contact us to discuss your project.